NewEvery arXiv paper, its researchers & institutions — mapped.
paper

Transient stability of a power system with superconducting fault current limiters

arXiv:cond-mat/0701308

Abstract

The influence of a superconducting fault current limiter (FCL) on the transient stability of the synchronic operation of electric machines is analyzed for different locations of the inductive FCL in a network and for different parameters of the device. It is shown that the stability can be improved or degraded depending on the FCL impedance under a fault and the time of the recovery of the initial state of the limiter after a fault. Improving the transient stability with the inductive superconducting FCL is demonstrated in the experiments on the electrodynamic model of a power system. The expansion of the obtained results for other FCL designs is discussed.

12 pages, 7 figures